NEC 2002: Table 250.66
| Grounding Electrode Conductor for AC systems | |||
| Size of Largest Ungrounded Service Entrance Conductor* (AWG/kcmil) | Size of Grounding Electrode Conductor (AWG/kcmil) | ||
| Copper | Aluminum | Copper | Aluminum | 
| 2 or smaller | 1/0 or smaller | 8 | 6 | 
| 1 or 1/0 | 2/0 or 3/0 | 6 | 4 | 
| 2/0 or 3/0 | 4/0 or 250 | 4 | 2 | 
| Over 3/0 through 350 | Over 
					250 through 500 | 2 | 1/0 | 
| Over 350 through 600 | Over 
					500 through 900 | 1/0 | 3/0 | 
| Over 600 through 1100 | Over 
					900 through 1750 | 2/0 | 4/0 | 
| Over 1100 | Over 1750 | 3/0 | 250 | 
| *or Equivalent Area for Parallel Conductors | |||
Click the icons below to get our NEC® compliant Electrical Calc Elite or Electric Toolkit for Android and iOS. The Electrical Calc Elite is designed to solve many of your common code-based electrical calculations like wire sizes, voltage drop, conduit sizing, etc. The Electric Toolkit provides some basic electrical calculations, wiring diagrams (similar to those found on this website), and other electrical reference data.
 
	