NEC 2014: Table 310.15(B)(16)

 

Allowable Ampacities of Insulated Conductors (no more than 3 current carrying conductors in raceway, cable, or Earth) based on Ambient Temperature of 30C.
Size Temperature Rating of Conductor Size
AWG or kcmil 60ºC 75ºC 90ºC 60ºC 75ºC 90ºC AWG or kcmil
(140ºF)  (167ºF)  (194ºF)  (140ºF)  (167ºF) (194ºF)
Types Types Types Types Types Types
TW
UF
RHW
THHW
THW
XHHW
RHH
THHN
XHH
XHHW
TW
UF
RHW
THHW
THW
XHHW
RHH
THHN
XHH
XHHW
Copper Aluminum
18 ---- ---- 14 ---- ---- ---- ----
16 ---- ---- 18 ---- ---- ---- ----
14 15 20 25 ---- ---- ---- ----
12 20 25 30 15 20 25 12
10 30 35 40 25 30 35 10
8 40 50 55 35 40 45 8
6 55 65 75 40 50 55 6
4 70 85 95 55 65 75 4
3 85 100 115 65 75 85 3
2 95 115 130 75 90 100 2
1 110 130 145 85 100 115 1
1/0 125 150 170 100 120 135 1/0
2/0 145 175 195 115 135 150 2/0
3/0 165 200 225 130 155 175 3/0
4/0 195 230 260 150 180 205 4/0
250 215 255 290 170 205 230 250
300 240 285 320 195 230 260 300
350 260 310 350 210 250 280 350
400 280 335 380 225 270 305 400
500 320 380 430 260 310 350 500
600 350 420 475 285 340 385 600
700 385 460 520 315 375 425 700
750 400 475 535 320 385 435 750
800 410 490 555 330 395 445 800
900 435 520 585 355 425 480 900
1000 455 545 615 375 445 500 1000
1250 495 590 665 405 485 545 1250
1500 525 625 705 435 520 585 1500
1750 545 650 735 455 545 615 1750
2000 555 665 750 470 560 630 2000

Back to Index of NEC Tables

Click the icons below to get our NEC® compliant Electrical Calc Elite or Electric Toolkit for Android and iOS.  The Electrical Calc Elite is designed to solve many of your common code-based electrical calculations like wire sizes, voltage drop, conduit sizing, etc.  The Electric Toolkit provides some basic electrical calculations, wiring diagrams (similar to those found on this website), and other electrical reference data. 